Scope
This section outlines the requirements for the construction of any food area and food support area in the following categories of premises:
AB, ME, PH, DSP, GIP, GD, PPH, APH, CKP, RSH.
Section 4.7.3: Plastic strips also applies to Section 7: Amenities and Section 13: Stores.
Section 4.10: Vermin Proofing also applies to Section 7: Amenities, Section 13: Stores and Section 16: Byproduct Facilities.
4.1 Outcome
Premises shall be constructed in accordance with good sanitary design principles, using materials that are suitable for the conditions of use, to facilitate the hygienic slaughter and dressing of animals and the processing, packing, storage and transport of food.
4.2 General Principles
4.2.1 Construction material approval
Construction materials complying with the requirements of this section can be used in premises licensed in terms of the Meat Act 1981 and approved premises. In addition, a current list of building materials that have been validated as meeting the requirements of this section and have been approved by MAF RA (M&S) for use in licensed and approved premises can be found in Manual 15: Approvals; "Building Materials and Equipment".
Materials shall be:
Materials shall be:
Materials shall be corrosion-resistant under the prolonged influence of corrosive agents encountered during the normal conditions of use, including water, water vapour, food ingredients and chemicals.
4.2.7 Inertness
Materials used in exposed product areas shall be inert to the food and cleaning materials encountered during normal conditions of use.
4.2.8 Thermal properties
Materials shall be capable of maintaining their original properties when subjected to temperature extremes that may occur during normal conditions of use. The thermal movement of materials shall be consistent with fixings, jointing systems and backing materials.
4.2.9 Colour
Surface finishes shall be of a colour which does not disguise contaminants.
| White or light coloured material has been found to be satisfactory. |
4.2.10 Resistance to discoloration
Materials should not stain when splashed with food components handled in the premises, acids or alkaline solutions, or other chemicals normally found in the premises.
4.2.11 Ease of repair and maintenance
Materials shall remain fit for purpose following repair and maintenance.
| Materials should be easy to maintain and repair without damage to surface areas or the integrity of the material. Manufacturers specifications should be adhered to. |
| 4.3.1 | Floors shall be constructed to be fit
for purpose. |
Floors shall be installed and maintained to eliminate all cracks, open joints, depressions or other low areas that would accumulate moisture or harbour contamination.
4.3.3 Grading
Floors subject to wet cleaning shall be adequately graded and drained so
that liquids do not accumulate.
| Floor falls of 1 in 50 have been found to be satisfactory in wet processing areas. Wash areas normally have a 1 in 25 fall. |
4.3.4 Junctions
Floor-to-wall junctions shall be constructed to facilitate easy cleaning
and, if subject to wet cleaning, shall be coved to provide a smooth
junction.
| Coving to a radius of 80 mm has been found to be satisfactory in wet cleaning areas. |
Interior walls shall be constructed to be fit for purpose.
4.5 Ceilings
Ceilings, including false ceilings, shall be constructed to be fit for purpose. Associated installations, equipment and fittings shall be designed and installed to facilitate effective cleaning.
4.6 Windows
| 4.6.1 | Windows shall be constructed to be fit for purpose. |
Windows should be flush with the inside surface of the wall. However, if the
sill has an inside ledge, this shall be sloped downwards at an angle to prevent
the build-up of dust and to facilitate effective cleaning.
| A window ledge angled to at least 45° has been found to be satisfactory. |
Glass windows shall not be used where glass could contaminate product if the
window broke.
| The use of safety glass is a satisfactory alternative. |
| 4.7.1 | Door openings and passageways shall be designed and constructed to ensure that unprotected food does not come into contact with the door jambs or walls. |
All doors opening from the exterior or byproduct areas directly to food areas or food support areas shall be, as far as practicable, self-closing. Alternatively, an ante room providing two doors between the room and the exterior or byproduct area would be an acceptable substitute for a self-closing door.
4.7.3 Plastic strips
Air curtains in doorways are not regarded as doors. Air curtains shall not be used in a way which will introduce contamination to unprotected food. Refer also to IS 2: Section 5.9.
4.8 Stairs, Decks and Walkways
| Side curbs at least 150 mm high measured at the front edge of the treads have been found to be acceptable. |
4.9 Protrusions Within the Hygiene Envelope
| 4.10.1 | Premises shall be designed and constructed to minimise the entrance and harbourage of vermin. |
| Opening windows, doorways, drains and other openings that would admit vermin should be equipped with effective vermin exclusion devices. |
| 4.10.2 | The location of any vermin control device shall not jeopardise the safety of food. |
New Zealand Food Safety Authority
68-86 Jervois Quay
PO Box 2835
Wellington
NEW ZEALAND
Phone: +64 4 894 2500
Fax: +64 4 894 2501
Contact