10.Refrigeration Facilities
Scope
This section outlines the specific requirements of refrigeration facilities within any of the following categories of premises:
S, AB, ME, PH, DSP, GIP, PPH, APH, RSH.
10.1Outcome
Refrigeration facilities shall be designed and constructed to be capable of reducing all parts of the food to the required preservation temperature within the required time, and/or holding and storing the food constantly at or below that temperature, and to minimise the possibility of contamination.
10.2General Principles
10.2.1Capacity
Refrigeration facilities shall be designed for the maximum capacity likely to be processed and held on the premises at any one time.
10.2.2Condensation
The design and construction of refrigeration facilities shall ensure that condensation drip on to carcasses, food or equipment is minimised.
10.2.3Rails and conveyors
Rails and conveyors on which unprotected carcasses and their parts are transported or held shall be designed and constructed to preclude contact of conveyed product with walls, floors, ceilings, structures, fittings, equipment and other product.
10.2.4Monitoring
Equipment for the accurate monitoring and display of temperatures shall be provided and shall operate at all times while refrigeration facilities are in use. Refer also to IS 2: Section 6.4.
10.2.5Temperature sensors
Temperature sensor(s) shall be positioned so they accurately monitor the temperature within a room using a sufficient number to monitor the temperature range in different
parts of the room. If only one temperature sensor is used it shall be located in the return air flow to the evaporator unit, as this usually has the highest temperature.
10.2.6Environmental loading facilities
Environmental loading facilities shall be designed and constructed to protect food from environmental hazards and to ensure maintenance of the temperature of food during load in or load out.
The minimum requirement for protected food loadout facilities is a canopy.
| Protection for unprotected food should be provided by means of sealed docking bays or fully enclosed environmental loading facilities. |
10.4Chillers
10.5Freezers
Facilities for freezing foods shall be designed and constructed to enable food to be reduced to the temperature, within a prescribed time, appropriate to the food and process. Refer also to Manual 6.
10.6Cold Stores
Chillers or freezers using a common refrigerated air supply with cold stores shall comply with the following requirements:
Ice that may come in contact with food directly or indirectly shall be made from potable water. Facilities shall be provided for its storage, handling and transport that will not contaminate the ice.